beautypg.com

Edwards Signaling FireShield 10 Zone User Manual

Page 38

background image

Programming

3.16

FireShield Technical Reference Manual

Format: 2 digits (0 – 9 and A – F)

Default: See Appendix E “Default event codes.” These can be
changed if needed.

Note:

If you are using Contact ID or the default 4/2 codes, you

can skip ahead to “End programming” now.

To change system event codes:

1. Press Reset or Signal Silence & Drill to scroll to the event

code that you want to change.

2. Press Reset to change the first digit of the code.

3. Press Panel Silence to save and advance to the next digit.

The trouble buzzer sounds a long beep as confirmation.

4. Press Reset to change the second digit.

5. Press Panel Silence to save.

6. Press Reset to advance to the next event code.

4. Set up or change IDC event codes

Description: Defines the 4/2 event codes (alarm, sup, trouble,
etc.) that are sent to the CMS for IDC events.

Format: 2 digits (0 – 9 and A – F)

Default: See Appendix E “Default event codes.” These can be
changed if needed.

To change IDC event codes:

1. Select an IDC for programming by pressing the Disable

button for that IDC.

2. Press Reset or Signal Silence & Drill to scroll to the event

code that you want to change.

3. Press Reset to change the first digit of the code.

4. Press Panel Silence to save and advance to the next digit.

The trouble buzzer sounds a long beep as confirmation.

5. Press Reset to change the second digit.

6. Press Panel Silence to save.

7. Repeat steps 1 through 6 for each IDC you want to

program.

8. Press Reset to advance to the next event code.

5. Set up or change the IDC zone restoration code

Description: Sets the 4/2 event code that is transmitted to the
CMS for an IDC restoral event.

Format: 1 digit (0 – 9 and A – F)

Default: See Appendix E “Default event codes.” This can be
changed if needed.

To change the IDC zone restoration code:

1. Press Reset to change the IDC zone restoration code.

2. Press Panel Silence to save and advance to the next

program option.

The trouble buzzer sounds a long beep as confirmation.

6. Set up or change the NAC trouble code

Description: Sets the 4/2 event code that is transmitted to the
CMS for a NAC trouble event.

Format: 2 digits (0 – 9 and A – F)

Default: See Appendix E “Default event codes.” This can be
changed if needed.

To change the NAC trouble code:

1. Select an NAC for programming by pressing the Disable

button for that NAC.

2. Press Reset to change the first digit of the code.

3. Press Panel Silence to save and advance to the next digit.

The trouble buzzer sounds a long beep as confirmation.

4. Press Reset to change the second digit.

5. Press Panel Silence to save.

6. Repeat steps 1 through 5 for each NAC you want to

program.

7. Press Reset to advance to the next program option.

7. Set up or change the NAC trouble restoration code

Description: Sets the 4/2 event code that is transmitted to the
CMS for a NAC restoral event.

Format: 1 digit (0 – 9 and A – F)

Default: See Appendix E “Default event codes.” This can be
changed if needed.

To change the NAC trouble restoration code:

1. Press Reset to change the NAC trouble restoration code.

2. Press Panel Silence to save and advance to the next

program option.

The trouble buzzer sounds a long beep as confirmation.

8. End programming

Programming is complete.

To end programming:

1. Press

Panel

Silence.

This manual is related to the following products: