Programming

3.4

FireShield Technical Reference Manual

Program option

Top LEDs/LCD

Setting

Bottom LEDs/LCD

Description

Auto Sig Sil

None

NACs stay on until Signal
Silence is pressed

Sil aft 20 mins

NACs automatically turn
off after twenty minutes

To program the auto signal silence timer:

1. Press Remote Disconnect to select the program option.

2. Press Reset to select your setting.

3. Press Panel Silence to save.

The trouble buzzer sounds a long beep as confirmation.

4. Program aux power reset

Description: Causes a temporary interruption of aux power
when Reset is pressed. This is so that four-wire smoke
detectors can be reset. If this is not programmed, pressing
Reset has no effect on the aux power output.

Caution:

This option must be set to No (continuous) if remote

annunciators or relays are being used.

Program option

Top LEDs/LCD

Setting

Bottom LEDs/LCD

Description

Aux Power Reset

No

Continuous 24 Vdc on
AUX PWR terminals

Yes

Resettable 24 Vdc on
AUX PWR terminals

To program aux power reset:

1. Press Remote Disconnect to select the program option.

2. Press Reset to select your setting.

3. Press Panel Silence to save.

The trouble buzzer sounds a long beep as confirmation.

5. Program signal silence/reset inhibit timer

Description: Programs all NACs with a one-minute silence
inhibit. This means that, the NACs cannot be silenced and the
panel cannot be reset during their first minute of activation.

Program option

Top LEDs/LCD

Setting

Bottom LEDs/LCD

Description

Sig Sil Inhibit

None

Signal Silence/Reset
operational immediately
after NACs turn on

Inhibit one min

Signal Silence/Reset
operational one minute
after NACs turn on

To program the signal silence/reset inhibit timer:

1. Press Remote Disconnect to select the program option.

2. Press Reset to select your setting.

3. Press Panel Silence to save.

The trouble buzzer sounds a long beep as confirmation.

6. Program IDC zone types

Description: Selects the type and functionality of each IDC.

Note:

See the FireShield ULI and ULC compatibility lists P/N

3100468 for restrictions.

Default: Alarm - unverified, with all NACs active

Program option

Top LEDs/LCD

Setting

Bottom LEDs/LCD

Description

Program IDC

Alarm-unverified

Alarm-unverified: For
circuits with smoke
detectors and contact
devices. All activations
are immediately
considered as alarms.
Circuit can not be
restored until devices are
restored to normal and
panel is reset.

Alarm-verified

Alarm-verified: For
circuits with smoke
detectors and contact
devices. 2-wire smoke
detector activations are
verified (delayed and
confirmed) before
activating an alarm. 4-wire
smoke detectors and
contact devices are not
verified and immediately
considered as alarms.
Circuit can not be
restored until devices are
restored to normal and
panel is reset.

Retard-waterflow

Waterflow (retard): For
connection of both vane
type and pressure flow
switches. Device
activation must be
maintained for at least 15
seconds before being
considered an alarm.
NACs activated by
waterflow IDCs can not be
silenced until activated
devices restore to normal
(panel reset not required).
Circuit can not be
restored until devices are
restored to normal and
panel is reset.