Edwards Signaling FireShield 10 Zone User Manual
Page 26
Programming
3.4
FireShield Technical Reference Manual
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Auto Sig Sil
None
NACs stay on until Signal
Silence is pressed
Sil aft 20 mins
NACs automatically turn
off after twenty minutes
To program the auto signal silence timer:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
4. Program aux power reset
Description: Causes a temporary interruption of aux power
when Reset is pressed. This is so that four-wire smoke
detectors can be reset. If this is not programmed, pressing
Reset has no effect on the aux power output.
Caution:
This option must be set to No (continuous) if remote
annunciators or relays are being used.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Aux Power Reset
No
Continuous 24 Vdc on
AUX PWR terminals
Yes
Resettable 24 Vdc on
AUX PWR terminals
To program aux power reset:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
5. Program signal silence/reset inhibit timer
Description: Programs all NACs with a one-minute silence
inhibit. This means that, the NACs cannot be silenced and the
panel cannot be reset during their first minute of activation.
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Sig Sil Inhibit
None
Signal Silence/Reset
operational immediately
after NACs turn on
Inhibit one min
Signal Silence/Reset
operational one minute
after NACs turn on
To program the signal silence/reset inhibit timer:
1. Press Remote Disconnect to select the program option.
2. Press Reset to select your setting.
3. Press Panel Silence to save.
The trouble buzzer sounds a long beep as confirmation.
6. Program IDC zone types
Description: Selects the type and functionality of each IDC.
Note:
See the FireShield ULI and ULC compatibility lists P/N
3100468 for restrictions.
Default: Alarm - unverified, with all NACs active
Program option
Top LEDs/LCD
Setting
Bottom LEDs/LCD
Description
Program IDC
Alarm-unverified
Alarm-unverified: For
circuits with smoke
detectors and contact
devices. All activations
are immediately
considered as alarms.
Circuit can not be
restored until devices are
restored to normal and
panel is reset.
Alarm-verified
Alarm-verified: For
circuits with smoke
detectors and contact
devices. 2-wire smoke
detector activations are
verified (delayed and
confirmed) before
activating an alarm. 4-wire
smoke detectors and
contact devices are not
verified and immediately
considered as alarms.
Circuit can not be
restored until devices are
restored to normal and
panel is reset.
Retard-waterflow
Waterflow (retard): For
connection of both vane
type and pressure flow
switches. Device
activation must be
maintained for at least 15
seconds before being
considered an alarm.
NACs activated by
waterflow IDCs can not be
silenced until activated
devices restore to normal
(panel reset not required).
Circuit can not be
restored until devices are
restored to normal and
panel is reset.