Calculations

A.2

FireShield Technical Reference Manual

Form A

Module

Quantity

Standby

current

(mA)

Qty

×

Standby

current (mA)

Alarm

current

(mA)

Qty

×

Alarm

current (mA)

FSRSI [1]

12

48

FSRZI-A [1]

8

35

FSRRM common [1]

30

41

FSRRM zone [1]

8

65

Other AUX

Total AUX [5] [6]

Form B
(Note: Calculate IDC detector load or use maximum load.)

IDC

Quantity of

detectors [2]

Detector current

(mA) [3]

Total standby current [4]

(quantity x current in mA)

IDC1

IDC2

IDC3

IDC4

IDC5

IDC6

IDC7

IDC8

IDC9

IDC10

Total current for all IDCs =

Max IDC standby current: FS302 = 4.5 mA, FS502 = 7.5 mA, and FS1004 = 15.0 mA

Notes
[1] Use of FSRSI, FSRZI-A, and FSRRM is limited as follows: Three- and five-zone panels support 2 FSRSIs, 2 FSRZI-As, and 4

FSRRMs, ten-zone panels support 2 FSRSIs, 4 FSRZI-As, and 6 FSRRMs.

[2] See the FireShield UL and ULC Compatibility List (P/N 3100468) for the maximum number of detectors per IDC.

[3] See FireShield UL and ULC Compatibility List (P/N 3100468) for detector current ratings.

[4] Maximum current per IDC may not exceed 1.5 mA.

[5] Aux power supplied by panel cannot exceed 0.5 A. If more than 0.5 A is required, you must use a compatible UL/ULC listed

fire alarm power supply.

[6] When using an auxiliary power supply, you must connect the -24 OUT connection on the panel to the negative connection on

the auxiliary power supply. Refer to the installation section for more information.