Programming

3.12

FireShield Technical Reference Manual

6. When you press Reset at the last digit (20th digit), the

system automatically advances you to the next program
option.

15. Enter the (DACR2) secondary phone number

Description: Specifies the secondary phone number that is
used to contact the central monitoring station.

Format: Up to 20 digits

Default: Blank

To enter the secondary phone number, follow the same steps
you used to enter the primary phone number. (See “Enter the
(DACR2) primary phone number” above.)

16. Enter the (DACR2) account code

Description: Sets the account code for DACR2. This is the
code that is used by the monitoring facilities receiver to
identify the panel location and response information.

Format: 4 digits

Default: FFFF

To enter the account code:

1. Press Reset until the first digit of the account code is

displayed.

2. Press Panel Silence to save and advance to the next digit.

The trouble buzzer sounds a long beep as confirmation.

3. Press Reset until the next digit is displayed.

4. Press Panel Silence to save and advance to the next digit.

5. Repeat steps 3 and 4 until all digits are entered.

6. When you press Reset at the last digit, the system

automatically advances you to the next program option.

17. Select the DACR2 alarm format

Description: Specifies the type of alarm protocol the DACR
will accept.

Settings: Contact ID

EST 4/2 (SIA DC-02 P3 with hexadecimal event codes)

Default: Contact ID

To select the DACR2 alarm format:

1. Press Reset to select the desired format.

2. Press Panel Silence to save and advance to the next step.

The trouble buzzer sounds a long beep as confirmation.

18. Select the restore option

Description: Determines whether or not restoration events are
sent to the second central monitoring station.

Settings: Send restores
No

restores

Default: Send restores

To select the restore option:

1. Press Reset to select the restore option for CMS two.

2. Press Panel Silence to save.

The trouble buzzer sounds a long beep as confirmation.

19. Enter retry count two

Description: Sets the maximum number of failed attempts to
deliver an alarm to a DACR.

Settings: 5 – 10 retries

Default: 5 (retries)

To enter retry count two:

1. Press Reset to change the retry count.

2. Press Panel Silence to save and advance to the next

program option.

The trouble buzzer sounds a long beep as confirmation.

20. Enter retry time two

Description: Sets the delay time before trying to resend an
alarm to a DACR.

Format: 2 digits max (5 – 10 seconds)

Default: 5 (seconds)

To enter retry time two:

1. Press Reset to change the retry time.

2. Press Panel Silence to save and advance to the next

program option.

The trouble buzzer sounds a long beep as confirmation.

21. Select tone or pulse dialing

Description: Specifies whether the phone line is set up for tone
dialing or pulse dialing.

Settings: Tone
Pulse

Default: Pulse

Note:

Touch tone is recommended where available.

To select tone or pulse dialing:

1. Press Reset to select tone or pulse dialing for line 1.

2. Press Panel Silence to save.

The trouble buzzer sounds a long beep as confirmation.