Yokogawa EJX440A User Manual
Page 66
<5. Parameter Summary>
5-5
IM 01C25T01-01E
Function
Label
Item
Contents
Default value
Handling
Fast key
sequences
Static
pressure
setup
A/G Select
Gauge/abs select for static pressure
Gauge or Absolute
Absolute
WD
1, 4, 1, 2, 7, 4, 1
Atm. Pres value
Conversion coefficient
101.3 kPa
WD
1, 4, 1, 2, 7, 4, 2
SP H/L Select
H/L select for static pressure
High or Low
High
WD
1, 4, 1, 2, 7, 5
SP Apply values
Rerange for static pressure
“0%, 100%, or Exit”
MD
1, 4, 1, 2, 7, 1, 2
SP Damp
Damping time constant for SP
0.00 to 100.00 sec
2.00 sec
WD
1, 4, 1, 2, 7, 3
SP LRV
Lower range value for static pressure Within measurement range
0.0 MPa
WD
1, 4, 1, 2, 7, 1,
1, 1
SP LSL
Lower sensor limit for static pressure
RD
1, 4, 1, 2, 7, 1,
1, 4
SP Min Span
Minimum span for static pressure
RD
1, 4, 1, 2, 7, 1,
1, 6
SP URV
Upper range value for static
pressure*
2
Within measurement range
WD
1, 4, 1, 2, 7, 1,
1, 2
SP USL
Upper sensor limit for static pressure
RD
1, 4, 1, 2, 7, 1,
1, 5
Status
Status group 1
Device status information for
hardware
R
1, 2, 1, 1, 1
Status group 2
Device status information for
hardware
R
1, 2, 1, 1, 2
Status group 3
Device status information for process
R
1, 2, 1, 1, 3
Status group 4
Device status information for process
R
1, 2, 1, 1, 4
Status group 5
Device status information for process
R
1, 2, 1, 1, 5
Status group 6
Device status information for settings
R
1, 2, 1, 1, 6
Status group 7
Device status information for settings
R
1, 2, 1, 1, 7
Status group 8
Device status information for settings
R
1, 2, 1, 1, 8
Status group 9
Device status information for settings
R
1, 2, 1, 1, 9
Tag
Tag
Tag number
8 alphanumerics
As specified
W
1, 3, 1
Temperature
compensation
T.Z. Cmp mode
Temperature compensation mode
Off or On
Off
W
1, 4, 2, ↓, 1
Temp Zero
Zero shift compensation
–99.999 to 99.999%/degC
0.000%/degC
W
1, 4, 2, ↓, 2
Temperature
sensor
Amp temp
Amplifier temperature
R
1, 4, 1, 3, 2
Snsr temp
Capsule temperature
R
1, 4, 1, 3, 1
Temp Unit
Temperature setting unit
degC, degF, or Kelvin
degC
W
1, 4, 1, 3, 3
Test key
Test Key
Special maintenance parameter
M
1, 4, 6
Transfer
function
Xfer fnctn
Output mode
Linear or Sq root
As specified or
Linear
W
1, 3, 5
Unit
Unit
Measurement range unit
See section 3.4.2
As specified or
kPa
W
1, 3, 2
SP Unit
Static pressure unit
See section 3.5.5
MPa
WD
1, 4, 1, 2, 3
Write protect
menu
Enable wrt 10min
Write protect release
8 alphanumerics
M
Hot key, 2, 2
New password
User set password for write protect
8 alphanumerics
M
Hot key, 2, 3
Software seal
Software seal
Keep or Break
Keep
R
Hot key, 2, 4
Write protect
Write protect indicator
Yes or No
No
R
Hot key, 2, 1
*1:
Handling:
R=Read only, W=Read & Write, M=Method, A=Applicable for option code AL, D=Applicable for differential pressure
transmitters. Do not change these parameters for pressure transmitters.
*2:
The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.