Operation – Yokogawa EJX440A User Manual
Page 31
<3. Operation>
3-21
IM 01C25T01-01E
1
F0334-1.ai
Select the
Scaled D/A trim item.
EJX:YOKOGAWA
Analog output trim
1 D/A trim
2 Scaled D/A trim
3 Clear D/A trim
HELP
SET
HOME
OK
EJX:YOKOGAWA
WARN-Loop should be
removed from
automatic control
DEL
SET
ABORT
OK
2
Press
OK (F4).
EJX:YOKOGAWA
Trim will be scaled
from 4.000 to 20.000
1 Proceed
2 Change
HELP
DEL
ABORT ENTER
3
Select
Change, and press
ENTER (F4).
When item 3.
Proceed is
selected,
D/A trim must be
carried out.
EJX:YOKOGAWA
Set scale- Lo output
value
4.000000
1
HELP
ABORT
4
Enter the value read on the meter
when the signal is 4 mA. In this
case, Enter the value of the
voltage across a 250Ω resistor
(1 V), and press
ENTER (F4).
DEL
ENTER
(OK)
(ENTER)
‘1’
EJX:YOKOGAWA
Set scale- Hi output
value
20.000000
5
HELP
ABORT
5
Enter the value read on the meter
when the signal is 20 mA. Then,
enter
5, and press ENTER (F4).
DEL
ENTER
(ENTER)
‘5’
Example 2: To adjust using a voltmeter
6
Select
Proceed and press
ENTER (F4).
EJX:YOKOGAWA
Trim will be scaled
from 1.000 to 5.000
1 Proceed
2 Change
HELP
SET
ABORT ENTER
EJX:YOKOGAWA
Connect reference
meter
DEL
SET
ABORT
OK
7
Connect the voltmeter, and press
OK (F4).
(OK)
(ENTER)
1. Device setup
2 Diag/Service
3. Calibration
2. Analog output trim
2. Scaled D/A trim
F0334-2.ai
EJX:YOKOGAWA
Enter meter value
1.000000
1.010
HELP
ABORT
9
9
8
Enter the reading of the voltmeter
(1.010), and press
ENTER (F4).
(The output of the transmitter
changes.)
DEL
ENTER
(ENTER)
(ENTER)
‘1 . 0 1’
EJX:YOKOGAWA
Scaled output: 1.000
equal readout
device?
1 Yes
2 No
HELP
ABORT
10
DEL
ENTER
Voltmeter reading: 1.010
If the reading on the voltmeter is
1.000, select
Yes and press
ENTER (F4).
If the reading is not 1.000, select
No. Repeat steps and until
the voltmeter reads 1.000 V.
Voltmeter reading: 1.000
11
Press
OK (F4). A 100% output
signal is output.
EJX:YOKOGAWA
Setting fld dev
output to 20mA
HELP
SET
ABORT
OK
EJX:YOKOGAWA
Enter meter value
5.000000
5.210
HELP
DEL
ABORT ENTER
12
EJX:YOKOGAWA
Scaled output: 5.000
equal readout
device?
1 Yes
2 No
HELP
DEL
ABORT ENTER
13
EJX:YOKOGAWA
NOTE-Loop may be
returned to automatic
control
HELP
ABORT
14
Enter the reading of the voltmeter
(5.210), and press
ENTER (F4).
DEL
OK
(ENTER)
“Returning fid dev to
original output”
(OK)
(ENTER)
‘5 . 2 1’
(OK)
Voltmeter reading: 5.210
Select
Yes and press ENTER
(F4).
Press
OK (F4).
Voltmeter reading: 5.000
EJX:YOKOGAWA
Setting fld dev
output to 4mA
HELP
DEL
ABORT
OK
8
Press
OK (F4). A 0% output
signal is output.
(OK)