<3. Operation>
3-30
IM 01C25T01-01E
F0353.ai
1. Device setup
4. Detailed setup
2. Signal condition
T.Z. Cmp menu
2. Temp Zero
Example: Enter K value obtained from the equation (a).
A value haivng up to 3 decimal places may be
specified.
When
h=+3 m, Fill fluid code A, span=15 kPa,
K=−(+3)Ч0.00745ч15Ч100=−0.149
EJX:
Temp Zero
0.000 %/degC
-0.149
ESC
ENTER
1
2
(ENTER)
HELP
DEL
Enter
−0.149
and press
ENTER
(F4).
‘ −0.149 ’
EJX:
T.Z. Cmp menu
1 T.Z. Cmp mode On
2 Temp Zero
HELP
SEND
HOME ENTER
Press
SEND (F2) to send the data
to the transmitter, then check to
confirm that disappears.
(SEND)
SEND
Note 1: The function is performed using a built-in temperature
sensor in the transmitter body. The temperature
deviation between the transmitter body and capillaries
should be minimized to achieve optimal performance
of the function.
Note 2: When the span changes, reenter the newly obtained
value of K to
Temp Zero.
Table A. Constant value [B] of fill fluid
Fill fluid
code
A, C
B
D
E
C
on
st
an
t v
al
ue
[B
]
mmH
2
O
0.76
0.87
1.45
0.75
kgf/cm
2
0.000076 0.000087 0.000145 0.000075
kPa
0.00745
0.00853
0.01422
0.00736
mBar
0.07453
0.08532
0.14220
0.07355
atm
0.000074 0.000084 0.000140 0.000073
inH
2
O
0.02992
0.03425
0.05709
0.02953
psi
0.00108
0.00124
0.00206
0.00167
mmHg
0.05592
0.06401
0.10669
0.05518
Note 3: Select the unit of constant value of [B] from the actual
unit used for the transmitter in operation.