Yokogawa EJX440A User Manual
Page 15
<3. Operation>
3-5
IM 01C25T01-01E
Item
HART
communicator
Description
Page
Monitoring
Pres and Pres %
Pressure variable and % output variable
—
AO
4 to 20 mA output variable
Snsr temp
Sensor temperature
SP and SP %
Static pressure variable and % static pressure variable
Engr Disp/exp/Unit
Displays the output of user setting engineering information
Maintenance Test output
Loop test
Used for loop checks. Output can be set freely from –2.5% to
110% in 1% steps
P.3-16
Diagnostics
Self test and Status
Check using the self-test and status command. If an error is
detected, the corresponding message is displayed
P.4-1
Output when CPU
error has occurred
AO Alm typ
Display the status of 4 to 20 mA DC output when a failure occurs
P.3-24
External volume
switch
Ext SW
Display/set the external volume protect/permit for LRV (URV)
setting
P.3-23
Software write
protect
Write protect
Displays the permit/protect status of setting changes depending
on communications
P.3-25
Enable wrt 10min
Write protect status is released for 10 minutes when the
password is entered
P.3-25
New password
Sets a new password
P.3-25
Adjustment
Zeroing
Zero trim
Sets the current input value to 0 kPa
P.3-17
Sensor trim
Pres and SP sensor
trim
Adjust the measured differential pressure and static pressure
variables
P.3-17
Analog output trim
D/A trim, Scaled D/A
trim
Adjust the output value at the points of 4 mA and 20 mA
P.3-20
Signal characterizer
S.C. menu
Used for compensate the output for the non-linear application
P.3-26
Capillary fill
fluid density
compensation
T.Z. Cmp mode
Compensates the zero shift by the ambient temperature effect
on the capillary tubes
P.3-29