Yokogawa EJX440A User Manual
Page 61
<4. Diagnostics>
4-21
IM 01C25T01-01E
Table 4.3.2 HART Communicator Error Messages
Error message
Probable cause
Countermeasure
Invalid selection
—
Change the setting.
Value was too high
Set value is too high.
Value was too low
Set value is too low.
Too few data bytes received
—
—
In write protect mode
Operation is set in the Write Protect mode. —
Lower range value too high
LRV set point is too high.
Change the range.
Lower range value too low
LRV set point is too low.
Upper range value too high
URV set point is too high.
Upper range value too low
URV set point is too low.
Span too small
Set span is too small.
Applied process too high
Applied pressure is too high.
Adjust the applied pressure.
Applied process too low
Applied pressure is too low.
New lower range value pushed upper
range value over upper senser limit
The shift of URV according to the new LRV
setting exceeds USL.
Change the URV setting within
the range of USL.
Excess correction attempted
Amount of correction is too much.
Adjust the amount.
Lowercase conversion not succeeded
Characters are not convertible. e.g. %
Correct the setting.
Not in fixed current mode
The fixed current mode is desired but not
set in that mode.
Set in the fixed current mode.
In multidrop mode
Operation is set in the multi-drop mode.
—
Not write protect mode
Operation is set without a password.
—
Lower range value and upper range value
out of limits
Set value is outside lower or upper range
limit.
Change the setting.