3 range change, Range change -9, Call up the keypad input display – Yokogawa EJX440A User Manual
Page 19
<3. Operation>
3-9
IM 01C25T01-01E
3.4.3 Range Change
The range values are factory-set as specified by
the customer. To change the range, follow the steps
below.
(1) Keypad input — LRV and URV
• The measurement span is determined by the
upper and lower range values. In this method,
the upper and lower range values can be set
independently, and the span changes according
to the range limit values sent to the transmitter.
1
F0310.ai
EJX:YOKOGAWA
Keypad input
1 LRV 0.0 mmH2O
2 URV 2500.0 mmH2O
3 Unit mmH2O
4 LSL -10197.2 mmH2O
5 USL 10197.2 mmH2O
HELP
SAVE
HOME ENTER
EJX:YOKOGAWA
LRV
0.0 mmH2O
0.0
HELP
DEL
ESC
ENTER
2
Enter
500, and press ENTER (F4).
EJX:YOKOGAWA
Keypad input
1 LRV 500.0 mmH2O
2 URV 2500.0 mmH2O
3 Unit mmH2O
4 LSL -10197.2 mmH2O
5 USL 10197.2 mmH2O
DEL
HOME
3
To change the Upper Range
Value, select the
URV item.
To change the Lower Range
Value, select the
LRV item.
HELP
SEND
ENTER
(ENTER)
‘3 5 0 0’
(ENTER)
‘5 0 0’
(SEND)
EJX:YOKOGAWA
URV
2500.0 mmH2O
2500.0
HELP
ESC
4
Enter
3500, and press ENTER (F4).
DEL
ENTER
EJX:YOKOGAWA
Keypad input
1 LRV 500.0 mmH2O
2 URV 3500.0 mmH2O
3 Unit mmH2O
4 LSL -10197.2 mmH2O
5 USL 10197.2 mmH2O
HELP
HOME
5
Press
SEND (F2) to send the
changed data to the transmitter.
Check that disappears.
SEND
ENTER
SEND
Example: To change the range from
0 to 2500 mmH
2
O to
500 to 3500 mmH
2
O
1. Device setup
3. Basic setup
3. Re-range
1. Keypad input
Call up the
Keypad input display.
NOTE
The calibration range can be set as LRV > URV
under the following conditions, reversing the 4 to
20 mA output signal.
LSL ≤ LRV ≤ USL
LSL ≤ URV ≤ USL
|URV – LRV| ≥ Min. Span