3.5.8 Trim Analog Output
Fine current output adjustment is carried out with
D/A trim or Scaled D/A trim.
•
D/A Trim
D/A trim is to be carried out if the calibration
digital ammeter does not exactly read 4.000 mA
and 20.000 mA with an output signal of 0% and
100%.
•
Scaled D/A Trim
Scaled D/A trim is to be carried out if the output
is adjusted using a voltmeter or a meter whose
scale is 0 to 100%.
1
F0333-1.ai
Select the
D/A trim item.
EJX:YOKOGAWA
Analog output trim
1 D/A trim
2 Scaled D/A trim
3 Clear D/A trim
HELP
SAVE
HOME
OK
EJX:YOKOGAWA
WARN-Loop should be
removed from
automatic control
DEL
SET
ABORT
OK
2
Press
OK (F4).
EJX:YOKOGAWA
Connect reference
meter
HELP
DEL
ABORT
OK
3
Connect the ammeter (±1µA is
measurable), and press
OK (F4).
EJX:YOKOGAWA
Setting fld dev
output to 4mA
HELP
ABORT
4
Press
OK (F4), and the
transmitter outputs a 0% output
signal.
DEL
OK
(OK)
(OK)
(OK)
EJX:YOKOGAWA
Enter meter value
4.000
4.115
HELP
ESC
5
Enter the read value
4.115 of the
ammeter, and press
ENTER (F4).
(The output of the transmitter
changes.)
DEL
ENTER
(ENTER)
‘4 . 1 1 5’
Example 1: For an adjustment using an ammeter (±1µA is
measurable)
1. Device setup
2 Diag/Service
3. Calibration
2. Analog output trim
1. D/A trim
Ammeter reading: 4.115
6
F0333-2.ai
If the reading on the ammeter is
4.000 mA, select
YES and press
ENTER (F4).
If the reading is not 4.000 mA,
select item 2.
NO. Repeat steps
and until the ammeter
reads 4.000 mA.
EJX:YOKOGAWA
Fld dev output 4.000
mA equal to reference
meter?
1 Yes
2 No
HELP
SET
ABORT ENTER
EJX:YOKOGAWA
Setting fld dev
output to 20mA
DEL
SET
ABORT
OK
7
4
4
5
5
Press
OK (F4), and the
transmitter outputs a 100% output
signal.
EJX:YOKOGAWA
Enter meter value
20.000
19.050
HELP
DEL
ABORT ENTER
8
Carry out the same procedures as
those described under and .
EJX:YOKOGAWA
Fld dev output 20.000
mA equal to reference
meter?
1 Yes
2 No
HELP
ABORT
9
Returning fld dev to original
output appears.
DEL
ENTER
(OK)
(ENTER)
(ENTER)
‘1 9.0 5 0‘
EJX:YOKOGAWA
NOTE-Loop may be
returned to automatic
control
HELP
ESC
10
Press
OK (F4).
DEL
OK
(OK)
(ENTER)
Ammeter reading: 19.050
Ammeter reading: 20.000
Ammeter reading: 4.000