[der`1] Channel 1 Derivative
Sets the derivative gain for ot 1. A value of 0.00 shuts the derivative off. This parameter
appears when the selected application software set uses temperature output 1 and
[type`] is set to [``Pid] and [Pid`U] is set to [```si].
Range: 0.00 to 9.99 minutes Default: 0.00 minutes

[Cycl1] Channel 1 Cycle Time
Sets the PID cycle time for output 1. This parameter only appears when the selected
application software set uses temperature output 1 and [type`] is set to [``Pid].
Range: 1 to 60 seconds Default: 5 seconds

[ProP2] Channel 2 Proportional Band
Sets the relative proportional band for output 2. This parameter only appears when the
selected application software set uses temperature output 2 and [type`] is set to
[``Pid].
Range: 1 to 999ºF (1 to 555ºC) Default: 25ºF (14ºC)

[rset2] Channel 2 Reset
Sets the reset (integral) gain for output 2. A value of 0.00 shuts reset off. This parame-
ter only appears when the selected application software set uses a temperature output
from channel 2 and [type`] is set to [``Pid] and [Pid`U] is set to [```US].
Range: 0.00 to 9.99 repeats / minute Default: 0.00 repeats / minute

[int`2] Channel 2 Integer
Sets the integral gain for output 2. A value of 0.00 shuts the integral off. This parame-
ter only appears when the selected application software set uses a temperature output
from channel 2 and [type`] is set to [``Pid] and [Pid`U] is set to [```si]. Range:
0.00 to 99.99 minutes / repeat Default: 0.00 minutes / repeat

[rate2] Channel 2 Rate
Sets the rate (derivative) gain for output 2. A value of 0.00 shuts the rate off. This
parameter only appears when the selected application software set uses temperature
output 2 and [type`] is set to [``Pid] and [Pid`U] is set to [```US].
Range: 0.00 to 9.99 minutes Default: 0.00 minutes

[der`2] Channel 2 Derivative
Sets the derivative gain for output 2. A value of 0.00 shuts the derivative off. This
parameter appears when the selected application software set uses temperature output
2 and [type`] is set to [``Pid] and [Pid`U] is set to [```si].
Range: 0.00 to 9.99 minutes Default: 0.00 minutes

[Cycl2] Channel 2 Cycle Time
Sets the PID cycle time for output 2. This parameter only appears when the selected
application software set uses temperature output 2 and [type`] is set to [``Pid].
Range: 1 to 60 seconds Default: 5 seconds