Tr o u b l e s h o o t i n g C h a r t

Note: For definitions of errors, see pages 56 - 57.

• Refer to sensor wiring instructions.
• Refer to controller specifications.
• System may need to warm up.

• Under-range Error has occurred on

channel 2.

• Controller measures a temperature

below the allowable operating range.

• Temperature sensor lead wires for

channel 2 are improperly terminated
(lead wires are reversed).

• Controller is misapplied.

[Err`11] appears on the

display

• Evaluate condition of channel 2 sen-

sor and circuitry.

• Confirm temperature sensor compati-

bility. Compare controller part num-
ber and specification to the chosen
sensor.

• Refer to the controller part number

on the sticker label, or view the con-
troller part number by accessing the
WatHelp Diagnostics Function.

• For controllers requiring thermocou-

ple sensors, confirm that the
[tc```] parameter is set to the
proper thermocouple curve.

• For controllers requiring RTD sen-

sors, confirm that the [rtd``]
parameter is set to the proper RTD
curve.

• Refer to sensor wiring instructions.
• Refer to controller specifications.

• A/D Overflow Error has occurred on

channel 2.

• Temperature sensor or circuit for

channel 2 is open or damaged.

• Temperature sensor for channel 2 is

incompatible with controller.

• Channel 2 measures a condition

above the controller temperature
range.

[Err10] appears on the

display

• Confirm temperature sensor compati-

bility. Compare controller part num-
ber and specification to the chosen
sensor.

• Refer to the controller part number

on the sticker label, or view the con-
troller part number by accessing the
WatHelp Diagnostics Function.

• For controllers requiring thermocou-

ple sensors, confirm that the
[tc```] parameter is set to the
proper thermocouple curve.

• For controllers requiring RTD sen-

sors, confirm that the [rtd``]
parameter is set to the proper RTD
curve.

• Refer to sensor wiring instructions.
• Refer to controller specifications.

• A/D Underflow Error has occurred

on channel 2.

• Temperature sensor for channel 2 is

incompatible with controller.

• Temperature sensor lead wires for

channel 2 are improperly terminat-
ed (lead wires are reversed).

• Channel 2 measures a condition

below the controller temperature
range.

[Err`9] appears on the

display

Possible Solutions

Possible Causes

Symptom/Indication