beautypg.com

Watlow MINICHEF 2000 User Manual

Page 41

background image

Tr o u b l e s h o o t i n g C h a r t

4 0

Wa t l o w M

I N I

C

H E F

2 0 0 0

H a r d w a r e & S o f t w a r e S e t u p G u i d e

Operations

Note: See definitions of temperature alarms on page 55.

• Verify the correct software

Application Number is programmed.
Access WatHelp Diagnostics and
make note of [APPL`] parameter
value.

• Refer to programming guide.
• Consult factory.

• Controller programmed incorrectly

for application.

• Factory applied wrong faceplate

overlay to system.

• Operator error.
• Defective key switch.

Keys seem to function dif-

ferently than expected.

• Turn power off, then on to clear the

temporary error.

• If error persists, return to factory.

• Temporary error.
• Controller is defective.

Scrambled display

• To silence the alarm, press the key

indicated by the flashing light.

• To select alternative Audible Alarm

sounds and duration, change value
of [Sound] parameter to meet the
application requirements. See pro-
gramming guide.

• Consult factory.

• Operator error.
• [Sound] parameter is set to

[````5].

• Controller requires reprogramming.

Alarm sound is on too long

or runs continuously at
the end of a Menu cycle.

Different Alarm sound or

duration is desired at the
end of a Menu cycle.

Press Menu key or Start/Stop key
for 2 seconds.

Operator error.

Cannot stop an active

menu.

• Access modes when controller is in

an idle state. User can cancel an
active menu in order to gain access
to these modes.

• Refer to programming guide for pro-

cedure to access the Menu
Programming Mode, the
Configuration Mode and for setting
the Real-time Clock time.

• Controller is currently running a

menu.

• Operator error.
• Controller does not have the Real-

time Clock option.

• Operator cannot access

Menu Programming
Mode.

• Operator cannot access

Configuration Mode.

• Operator cannot set Real-

time Clock time.

• Determine if High or Low Deviation

Alarms are required for channel 2.
If neither are required, access the
[AL``2] parameter and set the
value to disable the deviation
alarms, choosing [`nonE] or
[`Proc]. Refer to programming
guide.

• If Deviation Alarms for channel 2

are required, confirm that the
[ALdL2] parameter is set to the
proper value for the application.

• The Offset parameter can affect the

alarm point. Confirm that the
[OFSt2] parameter is set properly.

• System may require service.

Deviation Alarm indicating a low

temperature condition for channel
2.

• Channel 2 sensor measures a low

temperature that exceeds the allow-
able deviation below the pro-
grammed setpoint.

[`LO`2] appears on the

display.

System seems to be under-

heating.

Possible Solutions

Possible Causes

Symptom/Indication