Pv retransmit minimum output (85), Cascade primary loop number (86), Cascade base setpoint (87) – Watlow CLS200, MLS300 and CAS200 User Manual
Page 80: Cascade minimum setpoint (88), Cascade maximum setpoint (89)

74 Communications Specification
Chapter 3: Controller Parameter Descriptions
PV Retransmit Minimum Output (85)
This parameter specifies the minimum output (%) allowed for PV
retransmit calculation. Once set, the output will not drop below this
percentage. This number must not be higher than the maximum output
(command 83).
•
Range: 0 to 100.
•
Default: 0%.
Cascade Primary Loop Number (86)
This parameter specifies the cascade primary loop number to obtain the
output values. This number cannot be the same as the current loop.
Setting this to 0 disables the cascade feature for this loop.
•
Range: 0 (none) to MAX_CH.
•
Default: 0 (none).
Cascade Base Setpoint (87)
This parameter specifies the setpoint used as an offset for each loop.
•
Range: –999 to 9999 (depending on the precision in the primary
loop).
•
Default: 250 (25°F) for a J-type thermocouple.
Cascade Minimum Setpoint (88)
This parameter specifies the minimum allowable setpoint in the cascade
calculation. The resulting setpoint will not go lower than this. This
number must not be higher than the maximum setpoint (command 89).
•
Range: –999 to 9999 (depending on the precision in the primary
loop).
•
Default: 250 (25°F) for a J-type thermocouple.
Cascade Maximum Setpoint (89)
This parameter specifies the maximum allowable setpoint in the cascade
calculation. The resulting setpoint will not go higher than this. This
number must not be lower than the minimum setpoint (command 88).
•
Range: –999 to 9999 (depending on the precision in the primary
loop).
•
Default: 250 (25°F) for a J-type thermocouple.