Segment events and event states (57) – Watlow CLS200, MLS300 and CAS200 User Manual
Page 71
Chapter 3: Controller Parameter Descriptions
Communications Specification 65
•
Default: 0 (no trigger assigned).
Bits 0 to 3 determine the input number for the trigger:
Segment Events and Event States (57)
This parameter holds the event output number and event state for a
profile segment. Users can designate up to four events per segment; each
event takes 1 byte. Events are saved in memory as indicated below.
Seg(1) Event(1), Seg(1) Event(2), Seg(1) Event(3), Seg(1) Event(4),
Seg(2) Event(1), etc.
•
Range: Outputs 1 to 34 (except outputs used for control or for the
SDAC clock).
•
Default: 0 (no event assigned).
Here’s a bit map of the Event bytes:
Bit
Bit set to 0
Bit set to 1
0 to 3
See below
4 to 5
Reserved
6
Unlatched trigger (trigger
must remain true throughout
the segment).
Latched trigger (trigger
must be true at beginning of
segment).
7
Active Off
Active On
Bit 3
Bit 2
Bit 1
Bit 0
Input
Number
0
0
0
0
No trigger
0
0
0
1
1
0
0
1
0
2
0
0
1
1
3
0
1
0
0
4
0
1
0
1
5
0
1
1
0
6
0
1
1
1
7
1
0
0
0
8
Bit
Bit set to 0
Bit set to 1
0 to 5
Determines the output number for an event
6
Reserved
7
Event is active Off
Event is active On