beautypg.com

X0d return bus exception error count, X0e return slave message count, X0f return slave no response count – Watlow CLS200, MLS300 and CAS200 User Manual

Page 35: X0f force multiple coils, X10 preset multiple registers

background image

Chapter 2: Modbus-RTU Protocol

Communications Specification 29

operation, or power-up.

Subfunction

Data Field (Query)

Data Field (Response)

x00 0C

x00 00

CRC Error Count

x0D

Return Bus Exception Error Count

The response data field returns the quantity of Modbus-RTU

exception responses returned by the slave since its last
restart, clear counters operation, or power-up.

Subfunction

Data Field (Query)

Data Field (Response)

x00 0D

x00 00

Exception Error
Count

x0E

Return Slave Message Count

The response data field returns the quantity of messages

addressed to the slave, or broadcast, that the slave has pro-
cessed since its last restart, clear counters operation, or
power-up.

Subfunction

Data Field (Query)

Data Field (Response)

x00 0E

x00 00

Slave Message Count

x0F

Return Slave No Response Count

The response data field returns the quantity of messages

addressed to the slave for which it returned a no response
(neither a normal response nor an exception response),
since its last restart, clear counters operation, or power-up.

Subfunction

Data Field (Query)

Data Field (Response)

x00 0F

x00 00

Slave No Response
Count

x0F

Force Multiple Coils

Forces each coil (registers 00001 to 09999, the coils) in a sequence

of coils to either ON or OFF. When broadcast, the function forces
the same coil references in all attached slaves.

x10

Preset Multiple registers

Presets values into the sequence of holding registers (registers 40001

to 49999). When broadcast, the function presets the same register
references an all attached slaves.

NOTE

The function will override the controller’s memory protect
state. The preset values will remain valid in the registers
until the controller’s logic next solves the register contents.
The register values will remain if they are not programmed
in the controller’s logic.