56 Communications Specification

Chapter 3: Controller Parameter Descriptions

System Status (30)

The system status command consists of internal registers that flag
hardware and software exceptions. The system status command takes 4
bytes. (None of the controllers use the last 2 bytes; they are reserved.)

Here is a bit map of the first 2 system status bytes. More than 1 bit can
be set at a time.

Here’s a partial bit map of system status byte 2. The CLS and CAS use
bits 14 and 15 only.

System Command Register (31)

The System Command Register is a register of mode and configuration
flags for the controller’s processor.

Default: 0.

Bit

0

1

0

Battery OK

Dead battery

1

Init Start OK

Bad Init Start Bit

2

AIM OK

AIM comm failure

3

No Ambient Error

Ambient Error

4

No Ambient Warning

Ambient Warning

5

Zero Calibration OK

Bad zero calibration

6

Full scale calibration
value OK

Bad full scale calibration
value

7

Reserved

8

Alarms delay Off

Alarms delay On

9-13

Reserved

14-15

See next table

Bit 15 Setting

Bit 14 Setting

Result

0

0

Controller has 4 loops

0

1

Controller has 8 loops

1

0

Controller has 16 loops

Bit

0

1

0

Use default output data on
startup.

Use memory data on
startup.

1

Operator keys enabled.

Operator keys locked.

2

Unit set to 60 Hz.

Unit set to 50 Hz.

3

Ramp-soak time base in hours
and minutes.

Ramp-soak time base in
minutes and seconds.

4

Alarm digital outputs active
Low.

Alarm digital outputs active
High