beautypg.com

Ordering of heat and cool channel parameters, Ordering of ramp-soak profile parameters, Anafaze/ab protocol data table – Watlow CLS200, MLS300 and CAS200 User Manual

Page 23

background image

Chapter 1: ANAFAZE/AB Protocol

Communications Specification 17

Ordering of Heat and Cool Channel Parameters

For parameters that have both heat and cool settings the heat values are
stored in the first registers and the cool values are stored in the registers
starting at the listed address plus MAX_CH.

NOTE

Data table parameters 46 to 60 and 100 are ramp-soak
parameters. They are only used in controllers with the
ramp-soak option. Parameters 81 to 95 are enhanced fea-
tures and only available in controllers with the enhanced
features option.

Ordering of Ramp-Soak Profile Parameters

Ramp-soak profile parameters are ordered first by profile, then by
segment where applicable. So, for example, the first eight bytes of the
Ready Events parameter are the ready segment event states for the first
profile (profile A) and the next eight bytes are for profile B and so on. In
the case of the segment triggers, the first byte contains the first trigger
setting for the first segment of profile A, the second byte contains the
settings for the second trigger for the first segment of profile A, the third
byte contains the settings for the first trigger for the second segment of
profile A and so on.

Anafaze/AB Protocol Data Table

Number

Description

Address

in Hex

Type

Number of Bytes

0

Proportional Band/Gain

0020

UC

MAX_CH * 2

1

Derivative Term

0060

UC

MAX_CH * 2

2

Integral Term

00A0

UI

MAX_CH * 4

3

Input Type

0120

UC

MAX_CH

4

Output Type

0180

UC

MAX_CH * 2

5

Setpoint

01C0

SI

MAX_CH * 2

6

Process Variable

0280

SI

MAX_CH * 2

7

Output Filter

0340

UC

MAX_CH * 2

8

Output Value

0380

UI

MAX_CH * 4

9

High Process Alarm Setpoint

0400

SI

MAX_CH * 2

10

Low Process Alarm Setpoint

04C0

SI

MAX_CH * 2

11

Deviation Alarm Band Value

05A0

UC

MAX_CH

12

Alarm Deadband

0600

UC

MAX_CH

13

Alarm Status

0660

UI

MAX_CH * 2

14

Not used

06A0

128