Chapter 2: Modbus-RTU Protocol
Communications Specification 37
61
Output Limit
48147
1FD2
SI
MAX_CH * 2
62
Output Limit Time
48213
2014
SI
MAX_CH * 2
63
Alarm_Control
48279
2056
UI
MAX_CH
64
Alarm_Acknowledge
48312
2077
UI
MAX_CH
65
Alarm_Mask
48345
2098
UI
MAX_CH
66
Alarm_Enable
48378
20B9
UI
MAX_CH
67
Output Override Percentage
48411
20DA
SI
MAX_CH * 2
68
AIM Fail Output
48477
211C
UC
1
69
Output Linearity Curve
48478
211D
UC
MAX_CH
70
SDAC Mode
48544
215F
UC
MAX_CH * 2
71
SDAC Low Value
48610
21A1
SI
MAX_CH * 2
72
SDAC High Value
48676
21E3
SI
MAX_CH * 2
73
Save Setup to Job
48742
2225
UC
1
74
Input Filter
48743
2226
UC
MAX_CH
75
Loop Alarm Delay
48776
2247
UI
MAX_CH
76
Not used
48809
2268
1
77
Loop Names
(CLS/CLS200 and MLS/
MLS300)
48810
2269
UI
MAX_CH * 2
78
T/C Failure Detection Flags
(CLS/CLS200 and MLS/
MLS300)
48876
22AB
UC
MAX_CH
78
Channel Name
(CAS/CAS200)
48876
22AB
UC
MAX_CH * 8
79
Restore PID Digital Input
48909
22CC
UC
MAX_CH
80
Manufacturing Test
(CLS/CLS200 and MLS/
MLS300)
48942
22ED
UI
1
80
Manufacturing Test
(CAS/CAS200)
49014
2235
UI
1
81
PV Retransmit Primary Loop
Number
48943
22EE
UC
MAX_CH * 2
82
PV Retransmit Maximum
Input
49009
2330
UI
MAX_CH * 2
83
PV Retransmit Maximum
Output
49075
2372
UC
MAX_CH * 2
84
PV Retransmit Minimum
Input
49141
23B4
UI
MAX_CH * 2
85
PV Retransmit Minimum
Output
49207
23F6
UC
MAX_CH * 2
86
Cascade Primary Loop
Number
49273
2438
UC
MAX_CH
Number
Description
Absolute
Address
Relative
Address in
Hex
Type
Number of
Registers