Output linearity curve (69), Sdac mode (70), Sdac low value (71) – Watlow CLS200, MLS300 and CAS200 User Manual

Page 76: Sdac high value (72)

background image

70 Communications Specification

Chapter 3: Controller Parameter Descriptions

Output Linearity Curve (69)

This parameter lets users set heat and cool outputs to one of two
nonlinear output curves, or to Linear (no curve).

Range: Users can select 0 for no curve (linear), 1 for a slight curve,

and 2 for a more pronounced curve.

Default: 0 (no curve).

SDAC Mode (70)

This parameter toggles the SDAC between current and voltage output.

Range: 0 to 1, where 0 = voltage and 1 = current.

Default: 0.

SDAC Low Value (71)

This parameter sets a low range value for the output device. This value
must be less than the SDAC high value.

Range: 0 to 999 for voltage outputs and 0 to 1999 for milliamp out-

puts.

Default: 000 (0.00 volts) or 400 (4.00 mA).

SDAC High Value (72)

This parameter sets a high range value for the output device. This value
must be greater than the SDAC low value.

Range: 1 to 1000 for voltage outputs and 1 to 2000 for current out-

puts. (The controller displays this value with a fixed decimal place,
so the user sees a range of 1 to 10.00 for voltage inputs and 1 to
20.00 for current outputs.)

0

100

Linear

Curve 1

Curve 2