Relative and absolute modbus addresses, Modbus-rtu protocol data table – Watlow CLS200, MLS300 and CAS200 User Manual
Page 41
Chapter 2: Modbus-RTU Protocol
Communications Specification 35
Relative and Absolute Modbus Addresses
In the tables on the following pages, absolute addresses are in decimal
and relative addresses are in hexidecimal. Absolute addresses include
the type of register. Refer to the absolute address to determine which
function to use to read or write values (see the Function Codes on page
26).
Relative addresses indicate the register offset from the first register of
the particular type. For example, the first register for the Derivative
parameter is at 40067, which is offset 66 (x42) registers from the
beginning of the holding registers at 40001.
Modbus-RTU Protocol Data Table
Number
Description
Absolute
Address
Relative
Address in
Hex
Type
Number of
Registers
0
Proportional Band/Gain
40001
0000
UC
MAX_CH * 2
1
Derivative Term
40067
0042
UC
MAX_CH * 2
2
Integral Term
40133
0084
UI
MAX_CH * 2
3
Input Type
40199
00C6
UC
MAX_CH
4
Output Type
40265
0108
UC
MAX_CH * 2
5
Setpoint
40331
014A
SI
MAX_CH
6
Process Variable
40364
016B
SI
MAX_CH
7
Output Filter
40397
018C
UC
MAX_CH * 2
8
Output Value
40463
01CE
UI
MAX_CH * 2
9
High Process Alarm Setpoint
40529
0210
SI
MAX_CH
10
Low Process Alarm Setpoint
40562
0231
SI
MAX_CH
11
Deviation Alarm Band Value
40595
0252
UC
MAX_CH
12
Alarm Deadband
40628
0273
UC
MAX_CH
13
Alarm_Status
40661
0294
UI
MAX_CH
14
Not used
40694
02B5
33
15
Ambient Sensor Readings
40727
02D6
SI
2
16
Pulse Sample Time
40729
02D8
UC
1
17
High Process Variable
40730
02D9
SI
MAX_CH
18
Low Process Variable
40763
02FA
SI
MAX_CH
19
Precision
40796
031B
SC
MAX_CH
20
Cycle Time
40829
033C
UC
MAX_CH
21
Zero Calibration
40895
037E
UI
2
22
Full Scale Calibration
40896
037F
UI
2
23
Not used
40897
0380
1
24
Not used
40898
0381
1
25
Digital Inputs
10899
0382
Bit
MAX_DIGIN
26
Digital Outputs
00907
038A
Bit
MAX_DIGOUT