Input type (3) – Watlow CLS200, MLS300 and CAS200 User Manual
Page 52

46 Communications Specification
Chapter 3: Controller Parameter Descriptions
Input Type (3)
This parameter specifies the input type.
•
Range: 0 to 19 defined values.
•
Default: 1 (J-type thermocouple).
The following input types are currently defined:
The input type determines the ranges for these other parameters:
•
Process variable
•
Setpoint
Decimal
Number
Description
Hex
Value
Range
0
Linear
00
–10 to 60 mV (scaleable)
1
J-type thermocouple
01
–350 to 1400°F
–212 to 760°C
2
K-type thermocouple
02
–450 to 2500°F
–268 to 1371°C
3
T-type thermocouple
03
–450 to 750°F
–268 to 399°C
4
S-type thermocouple
04
0 to 3200°F
–18 to 1760°C
5
R-type thermocouple
05
0 to 3210°F
–18 to 1766°C
6
B-type thermocouple
06
150 to 3200°F
660 to 1760°C
7
Pulse Input (CLS, MLS, CAS)
07
0 to 2000 Hz
8
RTD1 (high resolution)
(Not available in CLS216/16CLS and CAS200/
CAS)
08
–148 to 527°F
–100 to 275°C
9
RTD2 (low resolution)
(Not available in CLS216/16CLS and CAS200/
CAS)
09
–184 to 1544°F
–120 to 840°C
10
Skip Channel
0A
N/A
11 to 13
Reserved for 8LS carbon potential
N/A
N/A
14
N/A
N/A
N/A
15
N/A
N/A
N/A
16
N/A
N/A
N/A
17
N/A
N/A
N/A
18
Nickel RTD
(Available in some MLS controllers)
12
–940 to 572°F
–700 to 300°C
19
Motor speed
13
–10 to 60 mV (scaleable)
20
E thermocouple
14
–328 to 1448°F
–200 to 787°C