Startup alarm delay (40), High process alarm output number (41), Low process alarm output number (42) – Watlow CLS200, MLS300 and CAS200 User Manual
Page 66: High deviation alarm output number (43), Low deviation alarm output number (44)
60 Communications Specification
Chapter 3: Controller Parameter Descriptions
•
Range: 0 to 255.
•
Default: 5.
Startup Alarm Delay (40)
This parameter designates a delay time for process and deviation alarms
on power-up. The controller does not report process and deviation
alarms for the specified number of minutes after the controller powers
up.
The startup alarm delay is a global alarm parameter; it applies to all
process and deviation alarms for every loop.
The startup alarm delay does not apply to failed-sensor alarms and AIM
failure alarms.
•
Range: 0 to 255 minutes.
•
Default: 0.
High Process Alarm Output Number (41)
This parameter assigns the output number to which the high process
alarm output is directed.
•
Range: 0 to 34.
•
Default: 0 (no high process alarm output).
Low Process Alarm Output Number (42)
This parameter assigns the output number to which the low process
alarm output is directed.
•
Range: 0 to 34.
•
Default: 0 (no low process alarm output).
High Deviation Alarm Output Number (43)
This parameter assigns the output number to which the high deviation
alarm output is directed.
•
Range: 0 to 34.
•
Default: 0 (no high deviation alarm output).
Low Deviation Alarm Output Number (44)
This parameter assigns the digital output number to which the low
deviation alarm output is directed.
•
Range: 0 to 34.