60 Communications Specification

Chapter 3: Controller Parameter Descriptions

Range: 0 to 255.

Default: 5.

Startup Alarm Delay (40)

This parameter designates a delay time for process and deviation alarms
on power-up. The controller does not report process and deviation
alarms for the specified number of minutes after the controller powers
up.

The startup alarm delay is a global alarm parameter; it applies to all
process and deviation alarms for every loop.

The startup alarm delay does not apply to failed-sensor alarms and AIM
failure alarms.

Range: 0 to 255 minutes.

Default: 0.

High Process Alarm Output Number (41)

This parameter assigns the output number to which the high process
alarm output is directed.

Range: 0 to 34.

Default: 0 (no high process alarm output).

Low Process Alarm Output Number (42)

This parameter assigns the output number to which the low process
alarm output is directed.

Range: 0 to 34.

Default: 0 (no low process alarm output).

High Deviation Alarm Output Number (43)

This parameter assigns the output number to which the high deviation
alarm output is directed.

Range: 0 to 34.

Default: 0 (no high deviation alarm output).

Low Deviation Alarm Output Number (44)

This parameter assigns the digital output number to which the low
deviation alarm output is directed.

Range: 0 to 34.