Output limit (61), Output limit time (62), Output limit (61) output limit time (62) – Watlow CLS200, MLS300 and CAS200 User Manual
Page 73
Chapter 3: Controller Parameter Descriptions
Communications Specification 67
*
The controller toggles a bit in the data-changed register to notify high
level software that the alarm status has changed.
Output Limit (61)
This parameter sets a limit on the output power percentage on either
heat or cool outputs for any loop. The output limit works with the output
limit time. While the limit is in effect, the output level will never exceed
the specified limit.
•
Range: 0 to 32700 (0 to 100%). Setting the limit to 100% (32700)
disables it.
•
Default: 32700 (100%), or disabled.
Output Limit Time (62)
This parameter describes the time span that the output limit is in effect.
•
Range: 0 to 999 seconds. Setting the output limit time to 0 makes the
output limit continuous; setting the output limit time from 1 to 999
seconds gives a range from 1 second to about 16 minutes.
•
Default: 0 seconds (continuous output limit).
The output limit only affects loops in automatic control (AUTO). The
time-out period is restarted whenever:
•
A loop switches from manual to automatic control.
•
The controller restarts.