Chapter 3: Controller Parameter Descriptions
Communications Specification 59
Process Power Digital Input (36)
Enable the thermocouple short detection feature by selecting a digital
input.
•
Range: 0 to 8 (Disabled = 0, Enabled = 1 to 8 indicating the selected
digital input).
•
Default: 0.
High Reading (37)
This parameter contains one of four points used to scale inputs. For
thermocouple and RTD inputs, the high reading is expressed in tenths of
a degree Celsius or Fahrenheit. For linear inputs, the high reading value
is expressed in tenths (CLS) or hundredths (MLS) of a percent of full
scale. For pulse inputs, the high reading value is expressed in Hertz.
•
Range: –999 to 9999 (CLS), –9990 to 11000 (MLS).
•
Default: 14000 (1400°F) for a J-type thermocouple.
Low Reading (38)
This parameter contains one of four points used to scale inputs. For
thermocouple and RTD inputs, the low reading is expressed in tenths of
a degree Celsius or Fahrenheit. For linear inputs, the low reading value
is expressed in tenths (CLS) or hundredths (MLS) of a percent of full
scale. For pulse inputs, the low reading value is expressed in Hertz.
•
Range: –999 to 9999 (CLS), –9990 to 11000 (MLS).
•
Default: –3500 (–350°F) for a J-type thermocouple.
NOTE
Note: Do not change High and Low Readings if the Input
Type is NOT set to Linear or Pulse.
Heat/Cool Spread (39)
This parameter describes a deadband about the setpoint for heat/cool
loops. The heat/cool spread is in units of the input variable. This
parameter is affected by the Precision parameter.
4
Extruder option not present
Extruder option
5
Ramp-soak not present
Ramp-soak
6
Math package not present
Math package
7
Reserved
Bit
0
1