Chapter 2: Modbus-RTU Protocol

Communications Specification 31

Examples

Read Examples

The data read must be sequentially located. If you’re reading a coil
rather than a register, you must offset the address by the location of the
bit you wish to read.

Sample Packet for Host Transmission

Sample Packet for Slave Transmission

Example

Slave

Address

in Hex

Function

in Hex

Start

Address

High

in Hex

Start

Address

Low

in Hex

Number

of Points

High

in Hex

Number

of Points

Low

in Hex

CRC
High

in Hex

CRC

Low

in Hex

1. Reading
PV of loop 2
(1600),
controller 1
(single-point
read)

01

03

01

6C

00

01

45

EB

2. Reading
loops 4 and 5
heat outputs,
of controller 3
(multipoint
read)

03

03

01

D1

00

02

94

2C

3. Reading
digital input
4, controller 1
(input status
read)

01

02

03

82

00

10

D9

AA

Example

Slave

Address

in Hex

Function

in Hex

Byte

Count

in Hex

Data

in Hex

CRC
High

in Hex

CRC

Low

in Hex

1. Reading PV of loop 2 (1600),
controller 1 (single-point read)

01

03

02

3E 80

84

1B

2. Reading loops 4 and 5 (50%,
60%) outputs (heat), of controller 3
(multipoint read)

03

03

04

3F DE 4C 4A

2D

41

3. Reading digital input 4, controller
1 (input status read)

01

02

02

08 00

BE

78