Use Recipes

This example assumes you have a project with at least one controller in which the recipe memory has
not already been used for something else.

In this example we will create a recipe that has five parameters from one controller. For each parameter
we will create a data transfer object that saves the parameter’s value in the recipe in the OIT. For these
objects the source addresses are the parameters’ Modbus addresses in the controller and the destination
addresses are RW (recipe word) addresses in the OIT. See the table.

Note: This example uses specific addresses internal to the OIT. If you have used one or more of these
for other purposes you will have to choose appropriate addresses for your project.

To create a recipe window and link it to the other screens:

1) Create and open a window to use for viewing, saving and loading recipes called “Recipe

Manager”.

2) Create a button on WINDOW 10 that opens the Recipe Manager window.

3) Create a button on the Recipe Manager window that opens window 10 Initial.

Note: Refer to the Trend example if necessary.

Repeat the following steps to add a data transfer object to the Recipe Manager screen for each
parameter you want to save in a recipe. Refer to the table below for addresses etc.:

Parameter

“Source” Address in Controller

Size in

Words

“Destination”

Recipe

Address

RMC

RMH

PM

ST

ST GTW*

Closed Loop Set Point

2501

5221

2161

22

2161

2

0

Alarm High Set Point

1741

2661

1481

98

1481

2

2

Heat Proportional Band

2231

4111

1891

233

1897

2

4

Integral

2235

4115

1895

227

1891

2

6

Derivative

2237

4117

1897

229

1893

2

8