Watlow Addendum to EZwarePlus User Manual
Page 27
6) Position the cursor centered in the top third of the window layout and click to place the text.
7) From the File menu choose Save.
Add a Numeric Display to the main window:
1) On the Objects menu,
click Numeric/ASCII
and choose Numeric
Display.
2) Click the General tab.
3) In Description type
Process Variable.
4) For PLC name choose
Modbus RTU Master
or Modbus TCP/IP
Master.
5) For Address choose
4x.and enter the
address of the Analog
Input 1 Process Value.
See the table.
(027)
For this controller…
This
parameter…
Enter this
Address*…
Choose this
Data Type…
RMCxxxx-xxxxxxx
Analog Input 1
Process Value
361
32-bit Float
RMHx-xxxx-x1xxx
381
32-bit Float
PMxxxxx-xxxxxxx
361
32-bit Float
STxx-xxMx-xxxx
20
32-bit Float
ST via RUI Gateway
361
32-bit Float
Other Controllers
Consult the controller manual.
*These addresses have already been changed to the absolute form required
for EZwarePlus by adding 1 to the value listed in the Watlow manual. Enter
them as listed.
6) Click the Numeric
Format tab.
7) In Data format set the
data type.
8) Set Right of decimal
Pt. to 1.
(028)
9) On the Font tab set
Align to Right.
10) Click OK.
(029)
Silver Series EM OIT
27
Watlow Addendum