Add a numeric display – Watlow Addendum to EZwarePlus User Manual

Page 18

background image

27) Double-click the meter

to open the Meter
Display Object’s
Properties
dialog.

28) Click the Profile tab.

29) Set X to 140.

30) Set Y to 60.

31) Set Width to 140.

32) Set Width (%) to 100.

33) Click OK.

34) From the File menu

choose Save.

(012)

Add a Numeric Display

This example assumes you have created a window in a project that is configured to communicate with a
Watlow Controller and that window is open in EZwarePlus.

1) On the Objects menu,

click Numeric/ASCII
then choose Numeric
Display
.

2) Click the General

tab.

3) In Description type

Actual Closed Loop
Set Point
.

4) For PLC name

choose Modbus RTU
Master
or Modbus
TCP/IP Master
.

5) For Address choose

4x and enter the
address of the Closed
Loop Working/Active
Set Point for your
controller. See the
table.

(013)

For this
controller…

This
parameter…

Enter this
Address*…

Choose this
Data Type…

RMCxxxx-xxxxxxx

Closed Loop
Working/Active
Set Point
(Read Only)

2513

32-bit Float

RMHx-xxxx-x1xx

5233

32-bit Float

PMxxxxx-xxxxxxx

2173

32-bit Float

STxx-xxMx-xxxx

204

32-bit Float

ST via RUI Gateway

2173

32-bit Float

Other Controllers

Consult the controller manual.

*These addresses have already been changed to the absolute form required
for EZwarePlus by adding 1 to the value listed in the Watlow manual. Enter
them as listed.

Silver Series EM OIT

 18 

Watlow Addendum