Ronan X96S MOLD LEVEL GAGE User Manual
Page 54
50
4 relay (2 Amp capacity) output points are provided. Form “C” outputs are brought out to the connector (three connections per
relay).
4 isolated open collector output points are provided. These outputs are capable of switching 4.5 to 30 Volts (externally supplied)
at a maximum of 50 mA.
24 volts DC is provided to be used as a wetting voltage when needed.
An isolated 15 volt DC power supply capable of providing 200 mA is also provided. The primary use of this power supply is to
power a quadrature encoder but can be used for other purposes if it is not required for this purpose.
X96-2009PL1
X96-2009PL1 is the Scintiallation Detector Interface Module. This optional
5
module provides:
• 1 isolated scintillation input (pulse counter, max signal 0-12
6
V, threshold 0.6 V)
• 1 head temperature input (1 uA per deg K)
• 1 non-isolated RTD (3-wire) input
• isolated power for the scintillation detector 24 V 40 mA supply
7
.
X96-2009PL2
X96-2009PL2 is the Scintillation Board with ch. 2 modified for 0-20 mA input instead of RTD
X96-2009PL3
X96-2009PL3 is the Scintillation Board with ch. 2 modified for 0-10Vdc input instead of RTD
X96-2029PL
X96-2029PL is the Mold Level Module (board) for scintillation detector, with two digital inputs, two analog outputs and two
digital outputs (1 relay, 1 TTL).
X96C148
X96C148 is the 85 to 230 Volt power supply module
X96C148-2
X96C148-2 is the 24 Volt DC power supply module
X96C148-4
X96C-148-4 is the 12 V DC “in”, 24 V DC “out” 50 watt power supply module
5
At least one detector interface module is required.
6
8.6 V nominal.
7
The power supply has the ability to control the power to the scintillation detector:
• when commanded by the CPU module,
• when the processor on the module detects a condition that could harm the scintillation detector,
• when the watchdog timer generates a reset.