35

Calibration

Calibration correlates the X96S's output to your actual mold level. It instructs the microprocessor to read and store the detector
counts for a low and high level of process. Once the system is conditioned to recognize the low and high level, it will provide a
4-20 mA output over the entire range of interest.

Step 1

Start at the Status Display

From the Status Display Screen, Press the F3 Key to display the
Password Screen (or the Main Menus if the password is disabled).

C

F1

F2

F3

F4

Ronan Engineering

X96S Mold Level Gage

Enter Password:

*

*****

All0

RST0

EXIT

ENTER

C

F1

F2

F3

F4

Ronan Engineering

X96S Mold Level
Status Display

Level 4.7500 in

MLM Ch.1 4.7500 in

Head Temp 92.00 degF
Filt Counts 1489

Raw Counts 1502

Time 08/04/06 08:05

Diagnostics

Lo-C Hi-C Back

Step 2 Password Menu

With the left most character * highlighted (All digits are set at
000000 at this point), enter in the password ‘101010’.
Press the

key 1 time to make the left most character equal to 1.

Press the

key 2 times to move to the third character.

Press the

key 1 time to make the third character equal to 1.

Press the

key 2 times to move to the fifth character.

Press the

key 1 time to make the fifth character equal to 1.

Press the F4 key (enter) to accept the password.
This will take you to the Main Menu.

Note: If the wrong password was entered, press the F1 (All0) to set
all the characters back to a value of 000000. You can begin to re-
enter the password from the beginning. Pressing the F2 (RST0) will
set the individual character that is highlighted back to the value 0.

Note: For security reasons, each character will always be displayed
as an asterisk

*

.