Ronan X96S MOLD LEVEL GAGE User Manual
Page 42
38
Step 1
Low Calibration using the
Local Auto Cal Feature
(Have the mold empty with mold water and oscillator running )
Press F1 Key (Lo-C) to perform an Auto Low calibration.
Read the next screen carefully and acknowledge the screen by
pressing the F4 Key. Wait until you see the counter reach 0.
Acknowledge the Low Counts = XXXX by pressing the F4 Key.
C
F1
F2
F3
F4
Ronan Engineering
X96S Mold Level
Status Display
Level 4.7500 in
MLM Ch.1 4.7500 in
Head Temp 92.00 degF
Filt Counts 1489
Raw Counts 1502
Time 08/04/06 08:05
Diagnostics
Lo-C Hi-C Back
C
F1
F2
F3
F4
Ronan Engineering
X96S
Mold Level
Status Display
WARNING –
Remove
loop from automatic
control, verify that
source is on and the
mold is empty
ABORT
OK
C
F1
F2
F3
F4
Ronan Engineering
X96S
Mold Level
Status Display
Calibrating gage...
10 seconds left
ABORT
OK
C
F1
F2
F3
F4
Ronan Engineering
X96S
Mold Level
Status Display
Low Counts = 18742
Press OK to accept
or ABORT to cancel
calibration
ABORT
OK
C
F1
F2
F3
F4
Ronan Engineering
X96S Mold Level
Status Display
Level 0.0000 in
MLM Ch.1 0.0000 in
Head Temp 92.00 degF
Filt Counts 18742
Raw Counts 18751
Time 08/04/06 08:05
Diagnostics
Lo-C Hi-C Back