Continuous Control Functions

RAMP SOAK BLOCK

3-17

38

Stop Input (STOPINP)........................................................................................................CWR
A FALSE to TRUE transition resets the profile to segment 1 and the mode to HOLD.

NONE

No Stop input configured. Attribute is not used.

local data

0

The initial local data value is FALSE (0).

source pointer

Any discrete source.

39

Run Input (RUNINP)...........................................................................................................CWR
A FALSE to TRUE transition sets the mode to RUN. This is used to start or resume the profile
when the mode is currently HOLD.

NONE

No Run input configured. Attribute is not used.

local data

0

The initial local data value is FALSE (0).

source pointer

Any discrete source.

40

Hold Input (HOLDINP) .......................................................................................................CWR
A FALSE to TRUE transition sets the mode to HOLD. This is used to pause the profile when
the mode is currently RUN. Specify a discrete input or NONE.

NONE

No Hold input configured. Attribute is not used.

local data

0

The initial local data value is FALSE (0).

source pointer

Any discrete source.

41

Skip Input (SKIPINP)..........................................................................................................CWR
A FALSE to TRUE transition skips a segment. If the current segment is not the last, the profile
will skip to the next segment. If the current segment is the last, the profile will go to the first
segment if repeat is YES or will be considered complete if repeat is NO.

NONE

No Skip input configured. Attribute is not used.

local data

0

The initial local data value is FALSE (0).

source pointer

Any discrete source.

101

Segment 1 Target Value (TVS1) .......................................................................................CWR
Value that the Result will stay at if this is a soak segment or it is the value that the Result will
ramp to if this is a ramp segment. Default value is 0.0

...

...etc 2 through 35

200

Segment 36 Target Value (TVS36) ...................................................................................CWR
Value that the Result will stay at if this is a soak segment or it is the value that the Result will
ramp to if this is a ramp segment. Default value is 0.0