Continuous Control Functions
RAMP SOAK BLOCK
3-11
04
Repeat Profile (REPEAT)...................................................................................................CWR
Repeat profile allows the whole ramp/soak profile to be repeated (YES). If NO, the ramp/soak
cycle will stop after the last segment.
NO
0
Stop ramp/soak cycle after last segment. Default is NO. When the
profile completes the last segment the Result and States A through D
will remain unchanged. The Active Segment Number (ACTSEG) will
be set to zero. The profile can be restarted by a Reset or Stop
command or by writing to the Active Segment Number attribute.
YES
1
Repeats ramp/soak cycle after last segment. The repeat function
permits the ramp/soak profile to be repeated automatically without
operator intervention. The entire profile is repeated each time the last
segment ends. Cycle Number (CYCNUM) indicates the active cycle
the profile is currently running in. This number starts at one and is
reset to one when the profile is reset. The cycle number stops
counting once the number reaches 65535.
05
Use Output States (USE)..................................................................................................... C-R
Each of the segments has four discrete output states. Select YES if you wish to use these
states, select NO otherwise.
NO
0
NO indicates States A through D are not required for segments. This
saves 4 bytes per segment of database space. Default is NO.
YES
1
YES indicates States A through D are to be used.
06
Startup Type (STYPE) .......................................................................................................CWR
Indicates the value that the profile will start from.
START VALUE
0
TRACK VALUE
1
PROCESS VALUE
2
Default is START.
07
Restart Mode (RESMODE) ................................................................................................CWR
This value is used to determine the block mode when the instrument is initialized due to a cold
or frozen restart. On a warm instrument restart, the block will continue in the mode it was in
before the restart.
RUN
0
Block mode is set to RUN when the instrument is initialized due to a
cold or frozen restart.
HOLD
1
Block mode is set to HOLD when the instrument is initialized due to a
cold or frozen restart.
PREVIOUS
2
Block mode is set to the previous mode (either RUN or HOLD) when
the instrument is initialized due to a cold or frozen restart. Default
value is PREVIOUS.