Micromod MOD: 1800P - MOD 30ML Identity Module (Version 2) PID and Ramp/Soak Functions User Manual
Page 54

Continuous Control Functions
RAMP SOAK BLOCK
3-14
22
State D (SD) ....................................................................................................................... CWR
This value will be the status of State D for the current segment.
23
State D Quality (SDQ) .........................................................................................................-WR
Quality of State D when Bad Inputs are REJECTED.
GOOD
0
If all of the inputs are good, then the ramp soak block updates State
D and the quality is set good. If bad inputs are accepted, then State D
Quality is set good.
BAD
1
If any of the inputs are bad, then the ramp soak block does not
update the State D and the State D quality is set bad.
24
Active Segment Number (ACTSEG) ................................................................................ CWR
The number of the currently active segment. Segment number 0 indicates an inactive profile.
Writing a 0 to the active segment number STOPs the profile cycle. Writing a valid segment
number to the active segment number will set the profile to the beginning of the written
segment number.
25
Active Segment Number Quality (ACTSEGQ) ..................................................................-WR
Quality of Active Segment Number
when Bad Inputs are REJECTED.
GOOD
0
If all of the inputs are good, then the ramp soak block updates Active
Segment Number
and the quality is set good. If bad inputs are
accepted, then Active Segment Number
Quality is set good.
BAD
1
If any of the inputs are bad, then the ramp soak block does not
update the Active Segment Number
and the Active Segment Number
quality is set bad.
26
Time Remaining (TREM)................................................................................................... CWR
Is the time remaining in a segment. When a soak segment is running this value can be written
to lengthen or shorten a soak time.
27
Time Remaining Quality (TREMQ).....................................................................................-WR
Quality of Time Remaining when Bad Inputs are REJECTED.
GOOD
0
If all of the inputs are good, then the ramp soak block updates Time
Remaining and the quality is set good. If bad inputs are accepted,
then Time Remaining Quality is set good.
BAD
1
If any of the inputs are bad, then the ramp soak block does not
update the Time Remaining and the Time Remaining quality is set
bad.