Diagnostics - error messages – Liquid Controls LCR 600 Setup & Op User Manual
Page 55

55
dIagnoStIcS - error meSSageS
NO FLOW STOP ERROR
The no flow timer expired and terminated the delivery. This is not an error condition. See the Delivery Setup 1 to
change the no flow timer.
POWER FAIL ERROR
The delivery ended due to a loss of input voltage. Check the power supply and wiring to the LCR 600. Check the in-
line fuse. See the troubleshooting section for more information (see page 65).
PReSeT eRROR
When accessing a preset field, a flash memory error was detected.
TeRMINAL NOT CONNeCTed
A terminal connection was disconnected during a delivery. Check the cables and connectors for broken wires and
loose connections.
dATA ACCeSS eRROR
A flash memory error occurred.
INIT WARNING
This message appears when No-Flow Timer or the Ticket Required?
fields return an error. If this error occurs,
the delivery can continue but default values 180 and Yes are used.
run tIme error meSSageS
These messages may be displayed if an error occurs while the system is running.
Invalid entry or entry out of range
The value entered into the field edit box is outside of the range
specified for the field. Reenter the value.
FLASH CRC FAILURe
The CRC stored with an LCR 600 data block indicates the data
or CRC has been corrupted. A rebuild operation could possibly fix
the problem. If not, try a clear all (Call Liquid Controls for clear all
instructions). If that does not work, hardware may be at fault and the
unit should be returned to Liquid Controls for more analysis. Before
starting a clear all operation, print a calibration ticket.
FLASH WRITE FAILURE
A failure detected while a data block was being written to the flash memory. See Flash CRC Failure above for
corrective actions
FLASH NOT INITIALIZed
The selector switch was not in the CALIBRATION position when a Clear All or Rebuild was attempted.
Invalid entry or entry out of range
The data entered was not within the required range limits for the specific field.
Duplicate flow rates not allowed
This message only appears when setting up multi-point calibration. When calibrating a multi-point meter, each
linearization point must have a unique flow rate. This message is displayed if a duplicate flow rate is entered.
Adjacent linearization points out of 0.25% range
This message only appears when setting up multi-point calibration. When calibrating a multi-point meter, adjacent
linearization points must be within a 0.25% correction of each other. To avoid this error, select an additional flow rate
and correction factor between the two points. More than one additional point may be required.