Maintenanceandtroubleshooting
red
leD
current
output
transistor
output
icon message dis-
played in the
info menu
possible cause
recommended action
OFF
4-20
mA
Switched
2)
"W:TRnPu 1:1
set"
In “Pulse” mode, the
volume entered for
a pulse is incorrect
(see chap. 9.12.10).
→
Enter an appropriate
volume.
→
check the K factor.
1)
if the DIAG MODE function of the "Output.AC1" or "Output.AC2" menu is set to "22 mA" (see chap. 9.12.9); else, the
current output delivers a standard current between 4 and 20 mA
2)
If the "PVAR" function of the "Output.TR1" and/or "Output.TR2" menus is set to "warning" (see chap. 9.12.10); else, the
transistor outputs are operating depending on the set thresholds.