Resetting totalizer 1 or totalizer 2 respectively, Adjusting the current outputs, Warning – Burkert Type 8076 User Manual
Page 58

56
Adjustmentandcommissioning
9.13.3. resetting totalizer 1 or totalizer 2 respectively
See chap. 9.10 to access the Calib menu.
System
Calib
Total 1
Reset Yes/No
Total 2
Reset Yes/No
TOTAL 1 or TOTAL 2 respectively: Reset (choice “Yes”) or do not reset (choice “No”) totalizer 1 or totalizer 2
respectively.
Totalizer 2 can be reset from Process level. See chap. 9.9.
9.13.4. Adjusting the current outputs
Warning
risk of injury due to wrong adjustment.
• Make sure the Hold mode is disabled (see chap. 9.13.1).
See chap. 9.10 to access the Calib menu.
Outputs
Calib
AC1 / AC2
4mA:
INPUT
20mA:
INPUT
The entered values are not memorised in this menu. Only the values emitted on the current outputs are
adjusted after pressing “OK” when the message “Recalibrate AC outputs?” is shown.
4mA: adjust the offset of current output 1 or current output 2.
When the "4mA" function is selected, the device generates a current of 4 mA: measure the current emitted by
the 4-20 mA output using a multimeter and enter the value given by the multimeter in the function "AC1.4mA" or
"AC2.4mA".
20mA: Adjust the span of current output 1 or current output 2.
When the "20mA" function is selected, the device generates a current of 20 mA: measure the current emitted by
the 4-20 mA output using a multimeter and enter the value given by the multimeter in the function "AC1.20mA" or
"AC2.20mA".
English
Type 8026- 8036- 8076