Burkert Type 8076 User Manual
Page 51
49
Adjustmentandcommissioning
UNIT: Choose the preferred time unit in which the flow rate is displayed.
Take care to choose the time unit according to the flow rate in the pipes as the display indicates a
maximum flow rate of 9999 volume units/time unit.
• If the flow rate measured is 0 ≤ volume unit/h ≤ 9999, choose the time unit “/h” so that the display indi-
cates a flow rate in volume units/h.
• If the flow rate measured is 1 ≤ volume unit/min ≤ 9999, choose the time unit "/min" so that the display
indicates a flow rate in volume units/min.
• If the flow rate measured is 1 ≤ volume unit/s ≤ 9999, choose the time unit "/s" so that the display indi-
cates a flow rate in volume units/s.
• If the flow rate measured is 0 ≤ volume unit/min or volume unit/s < 1, the display indicates a flow rate in
volume units/h, regardless of the time unit chosen.
• If the flow rate measured is ≥ 10000 volume unit/h, the display indicates a flow rate 166,66 ≥ volume
units/min ≤ 9999, regardless of the time unit chosen.
• If the flow rate measured is ≥ 10000 volume unit/min, the display indicates a flow rate 166,66 ≥ volume
units/s ≤ 9999, regardless of the time unit chosen.
• If the flow rate measured is 1 ≤ volume unit/min < 60, the display indicates a flow rate in volume units/
min, even if the time unit chosen is "/s".
selected time unit
measured flow rate
Displayed flow rate
/h
(default setting)
≥ 0 volume units/h and
≤ 9999 volume units/h
0 to 9999 volume units/h
≥ 10000 volume units/h
10000/60 volume units/min to 9999 volume units/min,
i.e.
166,66 volume units/min to 9999 volume units/min
≥ 10000 volume units/min
10000/60 volume units/s to 9999 volume units/s,
i.e.
166,66 volume units/s to 9999 volume units/s
/min
< 1 volume units/min
0 to 59,99 volume units/h
≥ 1 volume units/min and
≤ 9999 volume units/min
1 to 9999 volume units/min
≥ 10000 volume units/min
10000/60 volume units/s to 9999 volume units/s,
i.e.
166,66 volume units/s to 9999 volume units/s
/s
< 1 volume units/min
0 to 59.99 volume units/h
≥ 1 volume units/min and
< 60 volume units/min
1 to 59,99 volume units/min
≥ 1 volume units/s and
≤ 9999 volume units/s
1 to 9999 volume units/s
Attenuate the measurement variations on the display
FILTER: choose the filter level for the flow rate or frequency measured values displayed on the line selected.
Three damping levels are proposed: "slow" (slow filter), "fast" (fast filter) or "none" (no filter).
English
Type 8026- 8036- 8076