Adjustmentandcommissioning
When the device generates a "warning" or "error" event:
→
go into the "Info" menu to read the cause of the event generation.
→
and/or go into the "Sensor" function of the Diagnostic menu to read the measured input frequency.
→
if necessary, clean the paddle or the oval gears.
→
if necessary, check the process.
• The "warning" event may also be associated with one or other or both transistor outputs. See
chap. 9.12.9, function "Output.TR1" or "Output.TR2".
• The "error" event may also be associated with one or other or both current outputs. See chap. 9.12.10,
function "Output.AC1" or "Output.AC2".
• See also "If you encounter problems" at chap. 10.3
9.15. Test menu
9.15.1. modifying the Test menu access code
See chap. 9.10 to access the Test menu. The default access code is "0000".
Code
System
Test
0***
Confirm
0***
Enter the new
access code to the
TEST menu
Confirm the
new code
9.15.2. checking the outputs functions
See chap. 9.10 to access the Test menu.
The
T
icon is displayed in place of the
icon as soon as the check for the correct working of an output
has started. During the check the related output does not react according to the measured physical value.
AC1
AC1 Simul:
AC2 Simul:
AC2
TR1 Simul:
TR1
Test
Outputs
TR2 Simul:
TR2
OFF/ON
OFF/ON
INPUT
INPUT
AC1: check that current output 1 is working correctly by entering a current value in mA and then selecting "OK".
AC2: check that current output 2 is working correctly by entering a current value in mA and then selecting "OK".
TR1: check that transistor output 1 is working correctly by selecting the status of the transistor ("ON" or "OFF")
then "OK".
TR2: check that transistor output 2 is working correctly by selecting the status of the transistor ("ON" or "OFF")
then "OK".