Wiring, Electrical connections – Burkert Type 8076 User Manual
Page 29
27
Installationandwiring
Correct
Incorrect
Figure 15 :
The oval gear axes must be horizontal (seen from the front)
→
Fit the display module (see chap. 7.4) to parameter the device.
→
Assemble flowmeter type 8076 (see Figure 13)
→
Set the K factor parameter (see chap. 9.13.5) or have it determined through a teach-in procedure.
8.3.
Wiring
danger
risk of injury due to electrical voltage.
• Shut down and isolate the electrical power source before carrying out work on the system.
• Observe all applicable accident protection and safety regulations for electrical equipment.
• Use a high quality electrical power supply (filtered and regulated).
• Make sure the installation is equipotential. See chap. 8.3.3.
• Use a shielded cable.
• Once the device is wired, set the "HWMode" parameter depending on the wiring carried out, sink/NPN
or source/PNP. See chap. 9.12.8.
8.3.1.
electrical connections
number of fixed connectors
type of connectors
1 male M12 fixed connector
female 5-pin M12 (available as an accessory: see chap. 11)
1 male M12 fixed connector and 1 female
M12 fixed connector
female 5-pin M12 + male 5-pin M12 (both available as accessories:
see chap. 11)
8.3.2.
Assembling the male or female connector (accessories:
4
3 2
1
→
Unscrew the nut [1] on the body [4].
→
Insert the cable into the nut [1], the cable clamp [2] and the seal [3], and then into
the body [4].
English
Type 8026- 8036- 8076