25
Installationandwiring
8.2.1.
recommendations on installing an 8026 or an 8036 on a
pipe
attention
risk of damage when installing the fitting.
• Respect the installation instructions given in the user manual for the fitting.
→
Install the fitting on the pipe, respecting the instructions given in the manual for the fitting used.
→
Respect the following additional conditions of installation to ensure that the device operates correctly (Figure
11 and Figure 12).
- Install the device in such a way that the paddle wheel axis is horizontal.
- Prevent the formation of air bubbles in the pipe in the section around the sensor.
- Ensure that the pipe is always filled in the section around the sensor.
Figure 11 :
The paddle wheel axis must be horizontal
Correct
Correct
Incorrect
Incorrect
flow direction
Correct
Incorrect
Figure 12 :
Air bubbles within the pipe / Filling of the pipe
→
Fit the display module (see chap. 7.4) to parameter the device.
→
Assemble the flowmeter 8036 (see Figure 13) or install the flowmeter 8026 into the fitting S020 (see Figure
14)
English
Type 8026- 8036- 8076