32

Installationandwiring

14-36 V DC

+ -

+ -

1

2

3

4

Load 2

Load 1

4-20 mA input (external
instrument)

brown

grey

blue

white

black

Power supply

Figure 28 :

PNP wiring of both transistor outputs and wiring the current output in sourcing mode (parameter setting "PNP/
source"), of a version with 1 M12 fixed connector

8.3.6.

Wiring a version with two m12 fixed connectors and two
transistor outputs and two current outputs

1

2

3

4

Transistor output 1 (TR1)

Current output 1 (AC1)

0V

V+ (12-36 V DC)

male fixed connector

1

2

3

4

V+ (12-36 V DC)

Transistor output 2 (TR2)

Current output 2 (AC2)

0V

female fixed connector

Figure 29 :

Pin assignment of the male and female M12 fixed connectors

connect the power supply for the device to the male fixed connector; the supply is then
transferred internally to pins 1 and 3 of the female fixed connector in order to ease wiring of the
load to the female fixed connector.

pin of the female respectively male m12 cables available as accessories (order
code 438680 respectively 559177)

colour of the wire

1

brown

2

white

3

blue

4

black

5

grey

12-36 V DC

+ -

1

2

3

4

3

2

1

4

Load 1

(solenoid valve for

instance)

Load 2
(solenoid valve
for instance)

Power supply

white

blue

brown

grey

white

brown

Figure 30 :

NPN wiring of both transistor outputs (parameter setting "NPN/sink"), of a version with 2 M12 fixed connectors

English

Type 8026- 8036- 8076

This manual is related to the following products: