Current outputs – Burkert Type 8076 User Manual
Page 34
32
Installationandwiring
14-36 V DC
+ -
+ -
1
2
3
4
Load 2
Load 1
4-20 mA input (external
instrument)
brown
grey
blue
white
black
Power supply
Figure 28 :
PNP wiring of both transistor outputs and wiring the current output in sourcing mode (parameter setting "PNP/
source"), of a version with 1 M12 fixed connector
8.3.6.
Wiring a version with two m12 fixed connectors and two
transistor outputs and two current outputs
1
2
3
4
Transistor output 1 (TR1)
Current output 1 (AC1)
0V
V+ (12-36 V DC)
male fixed connector
1
2
3
4
V+ (12-36 V DC)
Transistor output 2 (TR2)
Current output 2 (AC2)
0V
female fixed connector
Figure 29 :
Pin assignment of the male and female M12 fixed connectors
connect the power supply for the device to the male fixed connector; the supply is then
transferred internally to pins 1 and 3 of the female fixed connector in order to ease wiring of the
load to the female fixed connector.
pin of the female respectively male m12 cables available as accessories (order
code 438680 respectively 559177)
colour of the wire
1
brown
2
white
3
blue
4
black
5
grey
12-36 V DC
+ -
1
2
3
4
3
2
1
4
Load 1
(solenoid valve for
instance)
Load 2
(solenoid valve
for instance)
Power supply
white
blue
brown
grey
white
brown
Figure 30 :
NPN wiring of both transistor outputs (parameter setting "NPN/sink"), of a version with 2 M12 fixed connectors
English
Type 8026- 8036- 8076