Recommendations on installing an 8076 on a pipe, Figure 13), Figure 14) – Burkert Type 8076 User Manual
Page 28
26
Installationandwiring
SE36
S030
1
2
3
SE36
S070
1
2
→
1: Insert the electronic module in the sensor holder.
→
2: Turn the electronic module by a quarter turn.
→
3: Secure the electronic module and the S030 fitting only, by
tightening the screw with a suitable tool to a max. tightening
torque of 1 Nm.
Figure 13 :
Assembling the SE36 and the fitting S030 or S070
A
B
→
Check that there is a seal on the fitting and that it is not
damaged. Replace the seal if necessary.
→
Place nut A on the fitting and insert circlip B into the groove.
→
Carefully insert the device into the fitting. If assembly is
correct, the device can no longer rotate on itself.
→
Secure the unit with nut A, tightening only by hand.
Figure 14 :
Installation of flowmeter 8026 into the fitting S020
→
Set the K factor parameter (see chap. 9.13.5) or have it determined through a teach-in procedure.
8.2.2.
recommendations on installing an 8076 on a pipe
→
Install the fitting S070 on the pipe in such a way that the oval gear axes are in the horizontal plane, as shown
in Figure 15.
English
Type 8026- 8036- 8076