Burkert Type 1150 User Manual
Page 70

68 - 1150
C
ONFIGURATION
Zero point resp. end value - Example: Setting with controller outputs for cooling.
The following settings have to be defined for double-setpoint controllers:
Zero point: 0 / End value: -100
NOTE
Analog outputs / Analog output 1 (2 to 6) / ...
Logic outputs / Logic output 1 (2 to 12) / ...
Value / selection
Description
Function
(Binary selector)
Outp. 1 contr. 1
Factory-set for logic output 2 to 12: Switched off
Output mode
none
Time delay
Pulse
Time delay:
The switch-on / switch-off edges can be delayed by a definable time period.
Pulse:
A definable pulse / pause ratio can be applied to the output.
ON time
- 1999 to 0 to + 9999
Delay of switch-on edge or pulse time.
OFF time
- 1999 to 0 to + 9999
Delay of switch-off edge or pulse time.
Value / selection
Description
Zero point
- 1999 to 0 to + 9999
A physical output signal is assigned to the value range of a output variable.
Example:
Setpoint 1 (value range: 150 to 500°C) is to be output via the analog output
(0 to 20 mA).
i.e.: 150 to 500 °C = 0 to 20 mA
Zero point: 150 / End value: 500
End value
- 1999 to 100 to + 9999
A physical output signal is assigned to the value range of a output variable.
Example:
see above "Zero point"
Offset
- 1999 to 0 to + 9999
Value of the parallel shift applied to the analog output values.