(2 to 16.) limit comparator – Burkert Type 1150 User Manual
Page 67
1150 - 65
C
ONFIGURATION
1. (2 to 16.) Limit comparator / ...
Range response: If a limit comparator is connected to an output, then the setting “Output
signal on over / underrange“ of the outputs has priority (see Chapter
Outputs).
NOTE
Value / selection
Description
LK function
No function
LK type 1
...
LK type 8
Limit comparator function.
-1999 to 0 to +9999
Limit value to be monitored.
Switching differential
0 to 1 to 100
Switching differential Xsd.
Action
Absolute
Relative
See explanation on next page.
Range response
Relay OFF
Relay ON
Function on over / underrange.
Switch-on delay
0 to 9999s
Delays the switch-on edge by a definable time period.
Switch-off delay
0 to 9999s
Delays the switch-off edge by a definable time period.
Acknowledgement
none
when inactive
when active
none:
The limit comparator is automatically reset.
when inactive:
The limit comparator must be acknowledged; acknowledgement is only possible
in the inactive condition.
when active:
The limit comparator must be acknowledged; acknowledgement is also possible
in the active condition.
Pulse time
0 to 9999s
The limit comparator is automatically reset after an adjustable time period.
LK process value
(Analog selector)
Switched off
Limit comparator process value.
LK setpoint
(Analog selector)
Switched off
Limit comparator setpoint.