Technical data, Visual representation – Burkert Type 1150 User Manual
Page 13

1150 - 11
S
YSTEM
DESCRIPTION
Visual Representation
Technical data
Thermocouple input
Input for resistance thermometer (RTD)
Designation
Measurement range
Meas. accuracy
1
Ambient
temperature
error
Fe-CuNi "L"
Fe-CuNi "J"
Cu-CuNi "U"
Cu-CuNi "T"
NiCr-Ni "K"
NiCr-CuNi "E"
NiCrSi-NiSi "N"
Pt10Rh-Pt "S"
Pt13Rh-Pt "R"
Pt30Rh-Pt6Rh "B"
W5Re-W26Re "C"
W3Re-W25Re "D"
W3Re-W26Re
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
DIN EN 60584
-200 to +900°C
-200 to +1200°C
-200 to +600°C
-200 to +400°C
-200 to +1372°C
-200 to +1000°C
-200 to +1300°C
0 to 1768°C
0 to 1768°C
0 to 1820°C
0 to 2320 °C
0 to 2495 °C
0 to 2400 °C
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
0.25%
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
100 ppm/K
Cold junction
Pt 100 internal, external or constant
1
With 250 msec sampling time.
Designation
Connection
circuit
Measurement
range
Meas. accuracy
1
Ambient
temperature
error
Pt100
DIN EN 60751
2-wire/3-wire
-200 to +850°C
0.05%
50 ppm/K
Pt 50,500, 1000
DIN EN 60751
2-wire/3-wire
-200 to +850°C
0.1%
50 ppm/K
Cu50
2-wire/3-wire
-50 to +200°C
0.1%
50 ppm/K
Ni100
DIN 43 760
2-wire/3-wire
-60 to +250°C
0.05%
50 ppm/K
KTY11-6
2-wire
-50 to +150°C
1.0%
50 ppm/K
PtK9
2-wire
lithium-chloride transducer
Sensor lead resistance
max. 30 ohms per lead for 2-wire or 3-wire circuit
Meas. current
250
A
Lead compensation
is not required for 3-wire circuit. With a 2-wire circuit, the lead resistance can be
compensated in software by a correction of the process value.
1
With 250 msec sampling time.