Controller, Controller 1 (2 to 4) / configuration – Burkert Type 1150 User Manual
Page 58

56 - 1150
C
ONFIGURATION
Controller
The following are set here: controller type, input variables of the controller, the
setpoint limits, conditions for manual mode and the presettings for selfoptimization
of the four controller channels.
Value / selection
Description
Controller type
2 point process controller
3 point process controller
3 point step
Position control
Continuous
2 point process controller
3 point process controller
3 point step automatic controller
Continuous automatic controller with integrated position control
Continuous automatic controller
Control action
Direct
Inverse
Direct:
The controller output Y is > 0 when the process value is smaller than the setpoint
(e.g. cooling).
Inverse:
The controller output Y is > 0 when the process value is larger than the setpoint
(e.g. heating).
Inhibit manual mode
Free
Inhibited
If the manual mode is inhibited, changing over to "manual" is not possible from
the keys or via the logic input.
Manual output
- 100 to 101
Defines the output after changing over to manual mode.
101 = last output
Range output
- 100 to 0 to 101
Output on out-of-range.
101 = last output