DeviceNetinstallation
11.8 network topology of a Devicenet system
Line with a trunk line and several drop lines.
Trunk lines and drop lines consist of identical material (see “Figure 39”).
Trunk line
DeviceNet cable
Terminating
resistor
120 Ω
¼ W
Terminating
resistor
120 Ω
¼ W
Drop lines
DeviceNet cable,
max. 6 m long
T01
Tn
Subscriber 1 (node 1)
Subscriber n (node n)
V +
V –
CAN_H
CAN_L
Figure 39:
Network topology - DeviceNet
11.9 configuring the control head
11.9.1 Dip switches
DIP switches for
bus address and baudrate
1 2 3 4 5 6 7 8
OFF
Figure 40:
DIP switches - DeviceNet
8 DIP switches are available for configuration:
• DIP switches 1 to 6
for the DeviceNet address
• DIP switches 7 to 8
for the baudrate
Danger!
risk of electric shock.
▶ Before working on equipment or device, switch off the power supply and secure to prevent reactivation.
▶ Observe applicable accident prevention and safety regulations for electrical equipment.